iCONEC®Copper Cable Solutions Cat.6A STP
Classification:
Cat.6A STP is mainly used for connections in building horizontal cables, EDA, HDA and other areas of the data center.
Cotnact:
Details Introduction
Cat.6A STP is mainly used for connections in building horizontal cables, EDA, HDA and other areas of the data center.
Product standards
• Comply with ISO / IEC11801&ANSI/TIA-568.2-D Cat.6A&UL Subject 444&YD/T1019 and other related standards.
• Comply with RoHS 2.0 and European Directive 2011/65/EU RoHS Compliance
• LSZH Cable: Flame retardant property conforms to: IEC60332-1 and IEC60332-3C; Toxicity standard: IEC60754-1; Acid gas concentration standard: IEC60754-2 smoke concentration standard: IEC61034-2
Characteristics
• 23AWG
• Central cross frame structure
• Frequency: 500MHz
• F/UTP, overall shielding with aluminum foil
• Maximum tension: 400N
• Maximum conductor resistance: 75Ω/km
• Insulating material: HDPE
• Material and Structural Dimensions
• Conductor: Solid copper conductor
• Shielding: F/UTP, overall shielding with aluminum foil, central cross frame structure. S/FTP, general shielding with screen mesh and individual shielding with aluminum foil for each pair.
• Insulation: Foamed PE
• Sheath: LSZH, CM, CMR, CMP and other flame-retardant classifications are provided.
Parameter
Main Technical Parameters
Content |
Technical Index |
Maximum resistance imbalance |
2% |
Insulation resistance |
>5000Mfi·km |
Characteristic impedance |
4-100MHz 100±15fi 101-250MHz 100±20fi 251-500MHz 100±25fi |
Delay skew |
≤ 45ns/100m |
Operation Temperature |
Installation Temperature: -20°C to +60°C Operation Temperature: -40°C to +70°C Cold bending: -20°C×4h no crack |
Permissible bending radius during installation |
8 times the outer diameter of the twisted pair. |
Bending radius |
Static for 10 times the cable diameter, dynamic for 20 times the cable diameter. |
Maximum tension |
400N |
Maximum conductor resistance |
75fi/km(23AWG) 95fi/km(24AWG) |
Insulating material |
HDPE |
Minimum insulation resistance |
100Mfi/km |
Dielectric strength |
500Vac/1min |
Package |
305m/box |
Content |
Technical Index |
Maximum resistance imbalance |
2% |
Insulation resistance |
>5000Mfi·km |
Characteristic impedance |
4-100MHz 100±15fi 101-250MHz 100±20fi 251-500MHz 100±25fi |
Delay skew |
≤ 45ns/100m |
Operation Temperature |
Installation Temperature: -20°C to +60°C Operation Temperature: -40°C to +70°C Cold bending: -20°C×4h no crack |
Permissible bending radius during installation |
8 times the outer diameter of the twisted pair. |
Bending radius |
Static for 10 times the cable diameter, dynamic for 20 times the cable diameter. |
Maximum tension |
400N |
Maximum conductor resistance |
75fi/km(23AWG) 95fi/km(24AWG) |
Insulating material |
HDPE |
Minimum insulation resistance |
100Mfi/km |
Dielectric strength |
500Vac/1min |
Package |
305m/box |
Product Model
Product Model |
Product Description |
iCONEC-CC6AFH13IW004 |
Cat 6a STP, F/UTP, LSZH-1, 23AWG, White, 305m/axis. |
iCONEC-CC6AFCM3BU004 |
Cat 6a STP, F/UTP, CM, 23AWG, Blue, 305m/axis. |
iCONEC-CC6AFCR3BU004 |
Cat 6a STP, F/UTP, CMR, 23AWG, Blue, 305m/axis. |
iCONEC-CC6AFVC3BU004 |
Cat 6a STP, F/UTP, PVC, 23AWG, Blue, 305m/axis. |
iCONEC-CC6AFH33IW004 |
Cat 6a STP, F/UTP, LSZH-3, 23AWG, White, 305m/axis. |
iCONEC-CC6ASH13IW004 |
Cat 6a STP, S/FTP, LSZH-1, 23AWG, White, 305m/box. |
iCONEC-CC6ASCM3BU004 |
Cat 6a STP, S/FTP, CM, 23AWG, Blue, 305m/box. |
iCONEC-CC6ASCR3BU004 |
Cat 6a STP, S/FTP, CMR, 23AWG, Blue, 305m/box. |
iCONEC-CC6ASVC3BU004 |
Cat 6a STP, S/FTP, PVC, 23AWG, Blue, 305m/box. |
iCONEC-CC6ASH33IW004 |
Cat 6a STP, S/FTP, LSZH-3, 23AWG, White, 305m/box. |